Cable Size Calculation | How To
0.6% is well below the 5% limit. The $25 \text mm^2$ cable is electrically sufficient.
Electricity flowing through a cable faces resistance, causing a drop in voltage. If the voltage at the end of the cable is too low, equipment won't work. Standard acceptable limits are usually for lighting and 5% for power. how to cable size calculation
$$I_\textrequired = \fracI_nk_1 \times k_2 \times k_3$$ If the voltage at the end of the
Suppose we need to calculate the cable size for a 10 kW load at 400V, with a cable length of 50 meters, and an ambient temperature of 30°C. $$I = \frac30,000\sqrt3 \times 415 \times 0
$$I = \frac30,000\sqrt3 \times 415 \times 0.85 \approx 49.2 \text Amps$$
Find the table for your and installation method .
The circuit breaker or fuse protects the cable. The breaker rating must be higher than the design current but lower than what the cable can handle. $$I_n \geq I_b$$